Contactor 500A 1000VDC normally open, Coil 48-72VDC with economiser, Auxiliary contacts
Remote battery switch for 48V batteries
0
DESCRIPTION
Relay type
- Contacts are open when the coil is unpowered which is defined as "1 Form A" or SPST-NO (single-pole, single-throw, normally open).
- Note: the contact surfaces on contactors wear down with every closure & opening of the contacts. Wear down on contact closure can be reduced by pre-charging the load circuit before closing the main contacts, particularly for high capacitance, high voltage loads. Arcing on opening the contacts can be eliminated by prior discharge of inductive circuits, eg alternators plus including flyback diode(s) and avalanche diodes to provide a circuit through which energy from inductors can be discharged safely.
Coil actuator specification (has built-in economiser to minimise holding current)
- Voltage (Will Operate) 32-95VDC (Valid Over Temperature Range)
- Voltage (Max.) 95VDC
- Pickup (Close) Voltage Max. 32VDC
- Hold Voltage (Min.) 22VDC
- Dropout (Open) Voltage (Min.) 18VDC
- Inrush Current (Max.) 1.3A
- Holding Current (Avg.) 0.03A@48V
- No back EMF
Main contacts specification
- Rated Operating Voltage up to 1000VDC
- Continuous (Carry) Current, Typical — 500 A @ 85°C, 400 mcm (202.7mm2) conductors
Auxiliary contacts specification
- Single pole-single throw normally open contact, "1 Form A"
- Current maximum: 2A @30VDC / 3A @125VAC
- Current minimum: 1mA @5V
Other performance data
- See attached datasheet
Product Facts
- HIGH CURRENT CARRY AND HIGH VOLTAGE: Inert gas filled arc chamber suitable for high voltage switching
- COMPACT STRUCTURE, LOW NOISE: Small, low-profile design with low noise while carrying or switching loads
- COIL ECONOMIZER: Economized coil for low power consumption
- SAFE FOR EXPLOSIVE ENVIRONMENTS: No arc leakage due to a hermetically sealed design
- HIGH RELIABILITY DESIGN: Hermetic sealing creates a stable environment for high voltage switching
- NO SPECIFIC MOUNTING ARRANGEMENT: Mountable in any orientation without reduction of performance
- VARIOUS APPLICATIONS: Battery disconnect, EV charging, energy storage systems, photovoltaics, power control, circuit protection and much more
Certification
-
Meet RoHS (2011/65/EU)
-
CE Certified
-
UL pending
SKU: AM-AEV250-GAN
SPECIFICATIONS
Coil actuator specification (has built-in economiser to minimise holding current)
- Voltage (Will Operate) 32-95VDC (Valid Over Temperature Range)
- Voltage (Max.) 95VDC
- Pickup (Close) Voltage Max. 32VDC
- Hold Voltage (Min.) 22VDC
- Dropout (Open) Voltage (Min.) 18VDC
- Inrush Current (Max.) 1.3A
- Holding Current (Avg.) 0.03A@48V
- No back EMF
| SKU: | AM-AEV250-GAN |
| Barcode: | |
| Model #: | AEV250-GAN |
| MPN: | AEV250-GAN |
Exotronic provides high-quality products and solutions tailored for B2B and commercial customers, including commercial businesses, caravan manufacturers, marine electricians, OEMs, as well as emergency services, and more.